Cold Aisle Containment in our server room

On Thursday 10 March 2011, we installed a so-called Cold Aisle Containment in the server room shared by the Department of Computer Science and HIIT. This is a rustic contraption made from transparent PE plastic, air-conditioning tubes, and a great deal of duct tape. It cuts back on the need to cool the server room very efficiently, as the air-tight plastic stops the intake and exhaust air from the servers from mixing.

After: http://www.youtube.com/watch?v=jZIuJIVYsDs
Before:   http://www.youtube.com/watch?v=ufb0PkCal2k

I videoed the setup before the change and after. The video may look like our server room is starting to resemble one of those biospheres that were popular in the 1990s. The advantage with transparent plastic as building material is that it puffs out with pressure, so now our maintenance team can monitor the cooling capacity of the computer room air conditioners (CRAC) by keeping an eye on the surface of the plastic. In this way, the CRACs will produce exactly as much cool air as the servers need.

Before installing the plastic bubbles in the server room, the CRACs were running full blast all the time. One of them pushed 15-degree (C) intake air under the floor, which became 19-21 degrees when it hit the servers because of the mixing of the air flows.At the end of our three hours of hard work this changed considerably, as the flow of exhaust air became more efficient, making work in the server room much more humane.

The intake air to the servers used to be 20 degrees, but now we need much less cooling capacity. We were able to shut down one CRAC completely and crank up two others 7 degrees. To adjust the last two devices, we need some special tools that we are still waiting for. We will continue to adjust the CRACs, as we are aiming at intake air of 22 degrees and to turn off one more CRAC unit.

Servers in the cold

In addition to optimising the server room, we have been running (other) servers outside since February 2010. At this moment, there is a 26U rack placed on the roof terrace of Exactum. It is protected from water and snow by a kind of cell. You can admire its winking lights at night in the images from the Exactum camera:

Near: http://www.cs.helsinki.fi/u/tkt_cam/exactum_terrace.jpg
Afar:  http://www.cs.helsinki.fi/u/tkt_cam/exactum.jpg

We are monitoring the servers constantly, and they are part of the Folding@home calculation. In addition, anyone can ask about the inner temperatures of the servers via a Twitter feed set up to monitor them. Twitter is in a state of perpetual beta, so more features are on the way.

Twitter:      http://twitter.com/HelsinkiChamber
Folding@home: http://fah-web.stanford.edu/cgi-bin/main.py?qtype=teampage&teamnum=200947

The intake server air is not filtered in any way. The most frequently asked question is, whether the moisture condensing inside the servers harms them. However, the condensation works in reverse, since the servers are cooled by air, so they are always warmer than the air around them. The next most frequent question is whether we could build a sauna with the exhaust air from the servers. We will return to this question in the near future.

If this or any other projects seem interesting to you, you can learn more on Thursday 17 March at the event "Science in the best of company" during the demo session at 17:30-20.

 

- Researcher Mikko Pervilä

You can also follow our research in our blog at http://blogs.helsinki.fi/pervila/.

Created date

17.03.2011 - 13:35

International Staff Get-together

On Friday 3rd of June the department and the international well-being group invited the international staff to a picnic and a guided tour on Suomenlinna. With several bags filled with delicious food and drinks we started in the late afternoon towards the island, where we found a sunny spot to enjoy the warm weather, the good company and of course the food: from bread over vegetables and fruits to cheese, we had it all. Besides the about 10 international attendees, also our head of department, Esko Ukkonen, found the time to join us.

Also, check out the new English speaking blog at http://www.cs.helsinki.fi/en/blog.

The story of the little games studio

Ninro gameMika Urtela and Hannu Pajula, graduates of the Department of Computer Science, are realising their piña colada-flavoured dreams in their game-producing company, Soul Aim Studios. This is the beginning of their story. The piña colada part of it has not come true yet, but they're working at it.

Jürgen Münch started as FiDiPro professor

 FiDiPro - the Finland Distinguished Professor Programme - enables distinguished international researchers to work and team up with the 'best of the best' in Finnish academic research. Financed by the Academy of Finland and Tekes, FiDiPro makes it possible to recruit highly merited scientists who are able to commit to long-term cooperation with a Finnish university or research institute.

In March 2011, the Department of Computer Science got its first FiDiPro professor, Jürgen Münch. Let’s interview Jürgen and learn to know him better.
 

Linus Torvalds made honorary alumnus in Kumpula

The Faculty of Science invited Linus Torvalds to be its honorary alumnus in Kumpula. During its alumni event, the faculty also named one of its lecture halls after Linus Torvalds. On the event held on Thursday 17 March, young researchers were the main speakers, and the 350 guests on the science campus gave them their full attention.