HIIT study: Servers run well around zero degrees

Lots of energy can be saved by using outside air directly for cooling in data centers in the north. In a study by researchers of Helsinki Institute for Information Technology HIIT and the University of Helsinki, computers functioned correctly over extended periods of time when run in harsh winter temperatures. Commercial, off-the-shelf computers ran well even when the outside temperature was -22C (-8F).

In the north, cooling data centers consumes lots of energy. According to an analysis published by HP in February 2009, data centers would be the sixth-largest consumer of electricity if they were classified as a separate industry. Research conducted in Helsinki Institute for Information Technology HIIT and the University of Helsinki aims at finding energy-saving potential in computing.

In the still on-going experiment by Professor Jussi Kangasharju and Researcher Mikko Pervilä servers have been kept running in a tent on a roof terrace in Finland for half a year. This is the first time computers have been run in a scientific experiment covering so wide a range of temperatures and humidity. Researchers follow how the servers run when temperatures and humidity changes naturally and the computers are only protected from direct snow, water and sunshine. When the outdoor temperatures have gone down to -22C (-8F), the temperature in the tent has been around -5C (+23F) because the computers heated up the tent.

- We are surprised at how well the servers have run compared to computers indoors. This means that data centers can be cooled in Northern Europe and Northern America with outside air efficiently without energy-consuming cooling and without computers functioning in a less stable manner due to changes in temperature and humidity, says Professor Kangasharju.

The study has been published in the Proceedings of the first ACM SIGCOMM workshop on Green networking.

Helsinki Institute for Information Technology HIIT is a joint research institute of Aalto University and the University of Helsinki for basic and applied research on information technology.

More information:

Jussi Kangasharju, professor

Helsinki Institute for Information Technology HIIT

Tel. +358 50 415 1708

e-mail: firstname.lastname@hiit.fi

Published article:

http://conferences.sigcomm.org/sigcomm/2010/papers/green/p9.pdf

Pictures about the experiments in Flickr:

http://www.flickr.com/photos/tags/runningserversaroundzerodegrees/

Presentation on the experiment held in Green Networking 2010:

http://www.cs.helsinki.fi/u/pervila/SIGCOMM2010/GreenNetworking_Presentation.pdf

Created date

11.10.2010 - 12:21

Cold Aisle Containment in our server room

On Thursday 10 March 2011, we installed a so-called Cold Aisle Containment in the server room shared by the Department of Computer Science and HIIT. This is a rustic contraption made from transparent PE plastic, air-conditioning tubes, and a great deal of duct tape. It cuts back on the need to cool the server room very efficiently, as the air-tight plastic stops the intake and exhaust air from the servers from mixing.

HIIT study: Servers run well around zero degrees

Lots of energy can be saved by using outside air directly for cooling in data centers in the north. In a study by researchers of Helsinki Institute for Information Technology HIIT and the University of Helsinki, computers functioned correctly over extended periods of time when run in harsh winter temperatures. Commercial, off-the-shelf computers ran well even when the outside temperature was -22C (-8F).

Master's degree studies in computer science popular among international applicants

Master's degree programmes in computer science at the University of Helsinki were very popular among international applicants in spring 2010. This academic year the department of computer science at the University of Helsinki decided to offer two of its Master's degree sub-programmes, namely the programme on Algorithms and Machine Learning and the programme on Networking and Services, completely in English from the beginning of Autumn term 2010.

Esko Ukkonen’s birthday coffee

The head of the department, Esko Ukkonen, celebrated his 60th birthday. The celebration was held in Exactum at the end of January. The party was attended by employees of the Department of Computer Science and invited guests. The programme included both congratulatory speeches and songs, with a quartet from Wiipurilaisen Osakunnan Laulajat (the Viipuri students’ association singers) singing a song for a former active member. Esko was inspector in Kymenlaakson Osakunta (the Kymenlaakso students’ association) for over ten years.